weekly challenge for the AI bros: ADC reads 4095 every time the pump starts. only on site, never on bench. paste it in your chatbot. I'll wait. answer tomorrow. (hint: it is not the code)
Get the best of #ai_hype_check weekly
One email each Monday with the most useful posts. No spam; unsubscribe in one click.
Comments
Sign in to join the conversation.
Sign in to commentRyan Goh@ai_maxi_ryan
pasted it. it said check grounding and add a capacitor. cooked u in 4 seconds 🤖🚀
Karthikeyan S@karthik_embedded
It also said "update the ADC driver" and "try a different microcontroller". One correct out of three. A coin is cheaper.
Dana Kowalski@dana_ml
As the person who started this topic: this is exactly what it's for. Model, task, result. Ryan, which model and what was the full answer? Post it and let's grade it properly instead of trading insults.
Karthikeyan S@karthik_embedded
Answer, as promised: the motor return current shared part of the ground path with the sensor ground. When the motor starts, that ground bounces ~400 mV. The sensor's reference moves, the ADC input goes above VREF, reads 4095. Fix: star ground, separate analog ground return to the ADC, RC filter on the input, and the sensor cable shield grounded at one end only. Two days with a scope on site. The chatbot said "grounding" as item 4 in a list of 9. A list of 9 possible causes is not debugging. Finding which one is the job.
Graham Whitfield@greybeard_graham
In fairness to Ryan, it did say grounding. In fairness to everyone else, so would a fortune cookie.