The pump that stopped every 40 minutes: a FreeRTOS priority inversion story

Karthikeyan S@karthik_embedded

August 24, 2026 · 3 min read

Field complaint: a pressure booster pump in an apartment building stops for 2 seconds roughly every 40 minutes. Water pressure drops, people on the 9th floor shout, the building manager calls our service guy, the service guy calls me. On the bench: nothing. Ran it for 3 days, no stop.

The system

STM32F4, FreeRTOS, three tasks that matter:

  • MotorControl, priority 5, runs every 1 ms, kicks the watchdog through a check-in
  • Comms (Modbus to the building BMS), priority 3
  • Logger, priority 1, writes events to UART for the service tool

Comms and Logger share one UART, protected by a semaphore. And MotorControl also sends a fault frame on the same UART when something is out of range. You can already see it, no? I could not, for 2 weeks.

What was happening

The "lock" was created with xSemaphoreCreateBinary(). A binary semaphore has no priority inheritance. So:

  1. Logger (prio 1) takes the UART lock and starts printing a long batch of events
  2. Modbus poll arrives, Comms (prio 3) becomes ready and preempts Logger. Logger still holds the lock
  3. MotorControl (prio 5) sees a small pressure spike, wants to send a fault frame, blocks on the lock
  4. Now the highest priority task is waiting for the lowest priority task, which cannot run because the medium priority task is busy
  5. Comms is busy for 180 ms because the BMS on this site polls a big block of registers. MotorControl misses its check-in, watchdog resets the MCU, pump stops 2 seconds

Why every ~40 minutes? The Logger flushes its batch every 40 minutes, and only on this site the BMS poll is big enough. On the bench we had no BMS. Classic Mars Pathfinder story from 1997, but in a building in Coimbatore.

How I found it

Four GPIOs, one per task, toggled at task entry and exit. Scope in normal trigger mode on the watchdog reset line, 4 channels, long memory. After a day of waiting on site with my laptop and a flask of filter coffee: MotorControl pin stops toggling, Logger pin high, Comms pin busy for 180 ms. Picture is very clear when you finally see it.

The fix (3 parts, the third one is the real one)

/* before */
uartLock = xSemaphoreCreateBinary();
xSemaphoreGive(uartLock);

/* after */
uartLock = xSemaphoreCreateMutex();      /* has priority inheritance */
faultQ   = xQueueCreate(8, sizeof(fault_t));

/* in MotorControl, every 1 ms */
if (fault_detected) {
    (void)xQueueSend(faultQ, &f, 0);     /* never block in the control loop */
}
  1. Mutex instead of binary semaphore. With priority inheritance, Logger is temporarily raised to priority 5 while it holds the lock, so Comms cannot preempt it
  2. Logger formats outside the lock, takes the lock only to push bytes into the DMA buffer. Lock held for microseconds, not milliseconds
  3. MotorControl never touches the UART. It drops fault frames into a queue with zero timeout and goes back to work. Comms sends them. The control loop does not wait for anybody, ever

Priority inheritance is a bandage. The real fix is design: the most important task should never share a lock with the least important one.

Pump is running 3 months now without a single stop. The 9th floor is quiet. My service guy bought me a coffee, which in our company is the highest award.

Get the best of #bare_metal weekly

One email each Monday with the most useful posts. No spam; unsubscribe in one click.

Comments

9

Sign in to join the conversation.

Sign in to comment
Diego Ramírez@diego_firmware#3 in Bare Metal
Mars Pathfinder!! every RTOS developer's favourite bedtime story. And it always comes back in a new form. Great writeup, the 4 GPIO trick is how I debug everything also
2 net votes
Matthias Kühn@m_kuehn#6 in Bare Metal
Classic. Your last sentence is the important one. Priority inheritance only bounds the blocking if the critical sections are short and not nested. In our projects a high priority runnable sharing a lock with a logger would not pass review.
0 net votes
Ondřej Hrubý@rewrite_it_in_rust#7 in Bare Metal
in Rust with RTIC this is impossible. resources are checked at compile time with priority ceiling protocol, no inversion, no runtime surprise. why you are still writing FreeRTOS in 2026? 🦀
2 net votes
Karthikeyan S@karthik_embedded#1 in Bare Metal
RTIC is nice, I agree, I have played with it. Now port 80,000 lines of motor control, re-certify, retrain 6 engineers and convince my management. I will wait.
1 net votes
Ondřej Hrubý@rewrite_it_in_rust#7 in Bare Metal
skill issue of your management then
2 net votes
Mehmet Aydoğan@malloc_mehmet#4 in Bare Metal
Rust kid again. Every thread. The man found a real bug in a real pump with a real scope and you come with "rewrite". Olmaz böyle şey. Karthik, good post. Second fix is the real fix. I would add: put a configASSERT that MotorControl never calls anything that can block. We have a macro that checks this in debug builds.
1 net votes
Matthias Kühn@m_kuehn#6 in Bare Metal
Enough. Back to the topic please.
0 net votes
Karthik Subramaniam@karthi_rustacean#8 in Bare Metal
As a Rust person: Ondřej, please stop. RTIC is good engineering, but the answer to a field bug in a FreeRTOS product is not "rewrite". You make all of us look bad.
1 net votes
Leo Chen 陈立@szhw_leo#2 in Bare Metal
Coffee from service guy is real award. Agree.
1 net votes